Question 1 of 8
1. Question
1 pointsReceptacles on 20 A circuit can have a rating of either 15 A or 20 A
Correct
Please Refer: NEC Code Table 210.21(B)(3)
Incorrect
Please Refer: NEC Code Table 210.21(B)(3)
-
Question 2 of 8
2. Question
1 pointsWhile measuring the distance between the receptacles wall space includes space measured around the corners is measured:
Correct
Please Refer: NEC Code 210.52(A)(2)(1)
Incorrect
Please Refer: NEC Code 210.52(A)(2)(1)
-
Question 3 of 8
3. Question
1 pointsA floor receptacle may be required if a balcony handrail is longer than ____ :
Correct
Please Refer: NEC Code 210.52(A)
Incorrect
Please Refer: NEC Code 210.52(A)
-
Question 4 of 8
4. Question
1 pointsReceptacles located more than ____ from the wall may not be counted as required receptacles:
Correct
Please Refer: NEC Code 210.52(A)(3)
Incorrect
Please Refer: NEC Code 210.52(A)(3)
-
Question 5 of 8
5. Question
1 pointsSliding panels in exterior walls are counted as wall space:
Correct
Please Refer: NEC Code 210.52(A)(2)(2)
Incorrect
Please Refer: NEC Code 210.52(A)(2)(2)
-
Question 6 of 8
6. Question
1 pointsAll receptacles that serve kitchen countertop surface shall have GFCI protection:
Correct
Please Refer: NEC Code 406.4(D)(3)
Incorrect
Please Refer: NEC Code 406.4(D)(3)
-
Question 7 of 8
7. Question
1 pointsEquipment grounding conductor shall be connected between non grounding type receptacle and the grounding type receptacle:
Correct
Please Refer: NEC Code 406.4(D)(2)(C)
Incorrect
Please Refer: NEC Code 406.4(D)(2)(C)
-
Question 8 of 8
8. Question
1 pointsA grounding type receptacle may be replace a non grounding type receptacle where the circuit is ground fault protected:
Correct
Incorrect